1. Nhanganyaya
The Extech 382252 is a comprehensive Earth Ground Resistance Tester Kit designed for accurate measurement of earth ground resistance. This kit provides three selectable ranges for earth ground resistance: 20 Ohms (Ω), 200 Ohms (Ω), and 2000 Ohms (Ω). Beyond earth ground testing, the device also functions as a multimeter, capable of measuring AC/DC Voltage, Resistance, and Continuity. It features automatic zero adjustment for ease of use. This manual provides detailed instructions for the safe and effective operation, maintenance, and troubleshooting of your Extech 382252.
2. Safety Information
Yambiro: Improper use of this meter can cause damage, shock, injury, or death. Read and understand all safety information and operating instructions before using this instrument. Always adhere to local and national safety codes.
- Usapfuure miganhu yepamusoro yekupinda chero basa.
- Exercise extreme caution when working with live electrical circuits.
- Ensure the meter is in good working condition and free from damage before use.
- Shandisa basa rakakodzera uye nzvimbo yakakodzera pakuyera.
- Tsiva mabhatiri kana chiratidzo chebhatiri chidiki chichioneka kuti uve nechokwadi chekuti kuverenga kwacho kwakarurama.
- Keep hands and fingers away from test probe tips when making measurements.
- Do not operate the meter in explosive atmospheres or in the presence of flammable gases or dust.
3. Package Zviri mukati
Ona kuti zvinhu zvese zviripo uye hazvina kukuvara pakuburitsa:
- Extech 382252 Earth Ground Resistance Tester
- Test Leads (set)
- Auxiliary Earth Bars (2 pieces)
- Kutakura Nyaya
- Protective Rubber Holster
- 1.5V AA Batteries (6 pieces)

Image 1: The Extech 382252 Earth Ground Resistance Tester Kit, showing the main unit, test leads, two auxiliary earth bars, and the carrying case.
4. Zvigadzirwa zveChigadzirwa
The Extech 382252 offers the following key features:
- Earth Ground Resistance measurement in three ranges: 20Ω, 200Ω, and 2000Ω.
- AC / DC Voltage measurement capabilities.
- Resistance and Continuity testing functions.
- Automatic zero adjustment for accurate readings.
- Yakakura, iri nyore kuverenga LCD kuratidza.
- Data Hold function to freeze displayed readings.
- Backlight for visibility in low-light conditions.
- Durable protective rubber holster.

Mufananidzo 2: Mberi view of the Extech 382252 Earth Ground Resistance Tester, highlighting its display, function dial, and control buttons.
5. Setup
5.1 Kuiswa kwebhatiri
- Iva nechokwadi chekuti mita yadzimwa.
- Tsvaga chivharo chebhatiri kuseri kwemamita.
- Use a screwdriver to remove the screw(s) securing the cover.
- Insert six (6) 1.5V AA batteries, observing correct polarity (+/-).
- Tsiva chivharo chekamuri yebhatiri uye chengetedza nescuru (s).
5.2 Kubatanidza Miedzo Inotungamira
Connect the test leads to the appropriate input jacks on the meter for the desired measurement function. For earth ground resistance testing, specific connections involving the auxiliary earth bars will be detailed in the operating instructions.
6. Operating Instructions
6.1 Simba On/Kudzima
Rotate the function dial from the 'OFF' position to any desired measurement function to power on the meter. To power off, rotate the dial back to the 'OFF' position.
6.2 Automatic Zero Adjustment
The meter features automatic zero adjustment. When selecting a resistance range, the meter will automatically adjust to zero, compensating for lead resistance. Ensure test leads are not shorted or open during this process for accurate zeroing.
6.3 Data Bata Basa
Press the 'HOLD' button to freeze the current reading on the display. Press it again to release the hold and resume live readings.
6.4 Basa reMarambi ekumashure
Press the backlight button (often indicated by a light bulb icon) to illuminate the display for better visibility in dark environments. Press it again to turn off the backlight.
7. Earth Ground Resistance Measurement
The Extech 382252 uses the 3-wire (or Fall-of-Potential) method for earth ground resistance measurements. This method requires the use of the two auxiliary earth bars provided.
7.1 Measurement Procedure (3-Wire Method)
- Kugadzirira: Ensure the circuit under test is de-energized and safely isolated.
- Placement of Auxiliary Earth Bars:
- Drive the first auxiliary earth bar (P) into the ground at a suitable distance from the earth electrode (E) being tested.
- Drive the second auxiliary earth bar (C) into the ground at a further distance from P, ensuring all three points (E, P, C) are in a straight line. Typical distances are 5-10 meters (15-30 feet) between E and P, and P and C, but may vary based on soil conditions and electrode size.
- Vatungamiriri veMiedzo yekubatanidza:
- Connect the 'E' terminal of the meter to the earth electrode under test.
- Connect the 'P' terminal of the meter to the first auxiliary earth bar (P).
- Connect the 'C' terminal of the meter to the second auxiliary earth bar (C).
- Sarudza Range: Rotate the function dial to the desired Earth Ground Resistance range (20Ω, 200Ω, or 2000Ω). Start with the highest range if the resistance value is unknown.
- Ita Muedzo: Press the 'TEST' button. The meter will inject a current and measure the voltage drop to calculate the earth ground resistance.
- Verenga kuyerwa: The resistance value will be displayed on the LCD.
- Simbisa Huchokwadi: For critical measurements, it is recommended to repeat the test with the auxiliary earth bars placed at slightly different distances to ensure the reading is stable and accurate.
8. Other Measurements
8.1 AC/DC Voltage Kuyera
- Connect the red test lead to the 'V' input jack and the black test lead to the 'COM' input jack.
- Rotate the function dial to the desired ACV (750V AC) or DCV (1000V DC) range.
- Batanidza ma test probe kudunhu rese kana chikamu kuti chiyerwe.
- Verenga bhukutage kukosha pachiratidziro.
8.2 Resistance Kuyera
- Ita shuwa kuti dunhu kana chikamu hachina simba.
- Connect the red test lead to the 'V' input jack and the black test lead to the 'COM' input jack.
- Rotate the function dial to the desired Resistance range (e.g., 200Ω, 20kΩ, 200kΩ).
- Batanidza test probes mukati mechikamu.
- Verenga kukosha kwekudzivisa pachiratidziro.
8.3 Kuenderera mberi Muedzo
- Ita shuwa kuti dunhu kana chikamu hachina simba.
- Connect the red test lead to the 'V' input jack and the black test lead to the 'COM' input jack.
- Rotate the function dial to the Continuity position (often indicated by a speaker icon).
- Connect the test probes across the component or wire.
- An audible beep indicates continuity (low resistance). The display will show the resistance value.
9. Kuchengeta
9.1 Kuchenesa
Wipe the meter with a dry, soft cloth. Do not use abrasives or solvents. Periodically clean the test leads and probes to ensure good electrical contact.
9.2 Kutsiviwa kwebhatiri
When the low battery indicator appears on the display, replace the batteries promptly to maintain measurement accuracy. Refer to Section 5.1 for battery installation instructions.
9.3 Kuchengeta
If the meter is to be stored for an extended period, remove the batteries to prevent leakage and damage. Store the meter in its carrying case in a cool, dry environment, away from direct sunlight and extreme temperatures.
10. Kugadzirisa matambudziko
- No Display/Meter Not Powering On: Check battery installation and ensure batteries are fresh. Verify the function dial is not in the 'OFF' position.
- Kuverenga Kusina Kurongeka: Ensure test leads are properly connected and not damaged. Check battery level. For earth ground resistance, verify proper placement and connection of auxiliary earth bars and ensure good contact with the ground.
- Hapana Kuenderera Beep: Check if the circuit is truly continuous. Ensure test leads are making good contact.
- Display Shows 'OL' (Overload): Ukoshi hwakayerwa hunodarika huwandu hwakasarudzwa. Chinja kune huwandu hwepamusoro.
Kana matambudziko akaramba aripo mushure mekutevera matanho aya, taura nerutsigiro rwevatengi.
11. Zvinotsanangurwa
| Tsanangudzo | Value |
|---|---|
| Brand | Extech |
| Model Number | 382252 |
| Earth Ground Resistance Ranges | 20Ω, 200Ω, 2000Ω |
| AC Voltage Range | Kusvika ku750V AC |
| DC Voltage Range | Kusvikira ku1000V DC |
| Resistance Ranges | 20Ω, 200Ω, 20kΩ, 200kΩ (typical, check device for full ranges) |
| Chiyero Chakarurama | +/-0.5% (for certain functions, refer to product manual for specifics) |
| Simba Source | 6 x 1.5V AA Mabhatiri |
| Item Weight | 0.69 Makirogiramu (1.52 makirogiramu) |
| Zviyero zveChigadzirwa (L x W x H) | 7.9 x 3.6 x 2 inches |
| Inosanganisirwa Zvikamu | Test leads, 2 earth bars, carrying case, holster, six 1.5V AA batteries |
| Safety Rating | CAT III 1000V, CE |
12. Warranty
The Extech 382252 Earth Ground Resistance Tester Kit typically comes with a 1-makore mashoma waranti from the date of purchase. This warranty covers defects in materials and workmanship under normal use. It does not cover damage resulting from misuse, accident, unauthorized repair, or modification. Please retain your proof of purchase for warranty claims.
13. Tsigiro
For technical assistance, calibration services, or further information regarding your Extech 382252, please refer to the official Extech website or contact their customer support department. Contact details can usually be found on the manufacturer's websaiti kana mune zvinyorwa zvinosanganisirwa nechigadzirwa chako.